We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Airzone 2 Odour Control Unit
Canopy Uk was built on experience, honesty, great value and giving customer service that is second to none.
With a strong team Canopy Uk is now one of the leading commercial kitchen extraction and kitchen ventilation companies in the UK.
Please call our sales team for help and support on 01733 700468
All Prices exclude VAT and Delivery
The OC2 has been specifically designed for use in commercial kitchens. The system injects ozone into the kitchen extraction canopy where it reacts with odours, which are oxidized in a chemical reaction, which results in the production of carbon dioxide and water vapour. The ozone itself is consumed during the process and is converted back into oxygen.
The benefits of purchasing an OC1 unit over traditional UV/Ozone systems are as follows:
- Compact, lightweight and quiet operation so is less obtrusive
- Quick and easy low cost installation
- Low capital and running costs – up to 50% less than traditional UVC systems
- Injection into ductwork – adding negligible back pressure to the system so requiring less energy to push air through the air handling system. This means less ductwork modifications
- The OC2 professional maintains efficiency as they remain outside of the air stream, they also require less maintenance and require less cleaning.
- Tested to EN13725:2003, CE Approved
Ozone Output | 20g/hr ozone output |
Housing dimensions | 290mm W 290mm L 290mm H |
Housing material | Stainless Steel powder coated black |
Duct work connection | 100mm circular |
Volume flow rate in ductwork | Up to 2m3/s per unit, subject to cooking odours |
Air residence time inside chamber | >0.1 seconds |
Pressure drop | N/A |
Weight of unit | 10Kg approx. |
Electrical requirements | 240V / 1ph / 50/60Hz |
Power requirements | 168W |
INSTALLATION
It is recommended to locate the units with an
injection point located closest to the source of odours (i.e. Canopy plenum or
nearest accessible point on ductwork, in order to maximize dwell time. In any
case the dwell time must be no less than 1 second.
The system is powered via a fused spur/socket, which
is interconnected to the main extraction fan control to ensure that the OC2
units only operate when the main fan is operating.
THE UNIT MUST BE INTERLOCKED INTO THE FAN CONTROL
SYSTEM
Delivery Group | Airzone Cube |
---|
Product Quality
All our canopies are manufactured in a quality controlled factory environment so we can make sure that the correct stainless steel is being used and no edges are left sharp. All parts to our products meet a high standard and are in accordance with governing bodies guidelines.
- experience
- honesty
- great value
Performance
Here at CanopyUk, when designing a canopy system, our project team will work alongside the client from start to completion to ensure that the system works well. We look at several points when a member of our team visits your site: plans on what you will be cooking, the capacity of the equipment and any further plans you might have for future expansion.
With this information this gives us an idea on what size canopy and type of fan you will require and how to plan the system. We pride ourselves on installing systems that work.